Emergency power supply SE-1000S
  Emergency uninterruptable power supply units of ServerPowerPlus AVR series are up-to-date source of power for various electronic equipment, mainly for computer systems to be used for professional purposes and in households. The application of a uninterruptable power supply unit eliminates 230V line interference. (over-voltages, current pulses, voltage decays) and ensures stable and dependable operation of computer systems.
  Emergency supply time is dependent upon the degree of charging of the accumulator and the load connected to the uninterruptable power supply unit and amounts 6 to 14 min.
  UPS (Uninterruptable power supply unit) is designed for work with the equipment of information systems, such as: computers, networks, servers, modems, as well as other electronic equipment, such as revenue cash registers and telephone exchanges.
Product features
Digital technology of voltage stabilisation
Digital technology of voltage stabilisation
Safe emergency power supply
Safe emergency power supply
Cold start
Cold start
Anti-voltage surge protection
Anti-voltage surge protection
Hold up time 6-14 min.
Hold up time 6-14 min.
Auto-overload protection
Auto-overload protection
Telephone filter
Telephone filter
Voltage filter
Voltage filter
5 cables: power supply , IEC x2, telephone, communications
5 cables: power supply , IEC x2, telephone, communications
Metal case
Metal case
Signalling: 4 LEDs
Signalling: 4 LEDs
Number of sockets
Number of sockets
 
Emergency power supply SE-1000S
Operating manual
Operating manual
in24en.pdf (324,6KB)
Download driver
Download driver
powerX3.zip (1,8MB)
See product picture
See product picture
SE-1000S_l.jpg (23,3KB)

Compare products
Print page
Add to basket
Show basket
The table below presents product’s basic technical specification. Additional information available from the downloadable documents, catalogue cards, leaflets, and operating manuals.
Technical specification
 
1000VA/700W
Power
 
here is
AVR
 
Input
 
Rated input voltage
~230V±10%
 
Rated input current
7,5A
 
Power grid/UPS switching threshold
~170V÷~280V
 
Input frequency
50Hz/60Hz
 
Output
 
Output voltage range
~230V±5%
 
Voltage control
~230V±5%
 
Power supply unit output frequency
50Hz±1%
 
Run pattern
Approximate sinusoid 230Vac±7%
 
<6 ms
Switching time
 
Batteries
 
Type
Sealed lead-acid accumulator, service-less
 
Hold up time (Pmax/Pmin)
6÷14 min
 
Charging time
8 hrs. up to 90% complete capacity
 
Battery type
12V 7Ah x 2
 
Auto-test and full accumulator charging protection
Battery protection
 
Auto-test - after every switching on
Auto-test
 
Electric protection
 
Protection against current surge
440 Joules
 
Protection against overload
106% , when load is 94%-106%, buzzer sounds. When load is over 106% continously, UPS will be turned off automatically within 90 seconds.
---
Fuse on input 6A
 
Voltage filtration
Interference eliminator RFI/EMI
 
RJ 45
Modem/Network protection
 
Communication with computer
 
Interface
RS232 (USB Adapter)
 
Software
Lestar PowerX3
Windows 98/ME/2000/NT/XP
 
Others
 
Dimensions (mm) long x wide x high
309x141x184
 
Weight
12,3 kg
 
Working conditions
Temp.0–35˚C up to 95% humidity
Storage does not cause condensation15-45˚C
 
Plug-in sockets
6 output sockets
 
Noise level
Up to 30 dB from a distance of 1 meter
 
5
Number of cables as standard
 
24
Warranty (months)
 
Standard CESERWIS drzwi do drzwi
 
 
 